HYGRASREG® RHT - 30Electronic HYGRASREG® RHT-30 room hygrostat and/or room thermostat with one continuous and two switching outputs, adjustable switching thresholds, with/without optional display for indicating ACTUAL humidity and/or ACTUAL temperature (accuracy class ±2.0% r.H.). The setpoints can be allocated to relative humidity and/or temperature. The sensor device is suitable for regulating and monitoring relative humidity (humidifying and dehumidifying) and/or temperature (heating and cooling) e.g. in ventilation and air conditioning ducts, laboratories, production facilities, climate test chambers, indoor swimming pools, greenhouses, etc., for humidifying and dehumidifying equipment or heating system control. The measuring transducer has been designed for exact humidity/temperature measurement. The RHT-30 uses a digital, long-term stable sensor as a measuring element. It is used in dust-free, unpolluted, non-aggressive air.
Collect
Voltage supply 24 V AC (± 20 %) and 15…36 V DC Power consumption < 1.5 VA/ 24 V DC, < 3.5 VA/ 24 V AC Load resistance RL > 5 kOhm Deviation of humidity typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 % Temperature deviation typically ± 0.2 K at +25 °C Output potential-free changeover contacts (2 x changeover contact 24 V, 1A ohmic load, separately adjustable, 1x 0 - 10 V) Sensor digital humidity sensor with integrated temperature sensor, low hysteresis, high long-term stability Operating difference Mode 1: both switch steps are freely adjustable (rel. humidity) Mode 2: 5 % between both switch steps (rel. humidity) Mode 3: both switch steps freely adjustable (temperature) Mode 4: switch step 1 (temperature), switch step 2 (rel. humidity) (adjustable via DiP switches) Setting range 5...95 % r.H. (Humidity) +5...+ 45 °C (Temperature) (switch steps 1 and 2 are separately adjustable) Ambient temperature storage –35...+85 °C, operation – 30...+70 °C, non-precipitating Electrical connection 0.14 - 1.5 mm² via terminal screws Housing plastic, material ABS, colour pure white (similar to RAL 9010) Housing dimensions 98 x 98 x 35 mm (Baldur 2) Installation wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes, for attachment to vertically or horizontally installed in-wall flush boxes for rear cable entry, with predetermined breaking point for cable entry from top/ bottom in case of plain on-wall installation Long-term stability ± 1 % per year Protection class III (according to EN 60 730) Protection type IP 30 (according to EN 60 529) Standards CE conformity, EMC directive 2014/ 30/ EU Function Humidifying/heating: 1st step: wire contacts 11 - 12. 2. step: wire contacts 21 - 22. Dehumidifying/cooling: 1st step: wire contacts 11 - 13. 2. step: wire contacts 21 - 23. |