HYGRASGARD® RPFTF - Modbus - T3Calibratable room pendulum humidity and temperature sensor HYGRASGARD® RPFTF - Modbus - T3 (± 2,0 %) or RPFTF - 20 - Modbus - T3 (± 1,8 %), with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, cable sensor with a stainless steel pendulum and a plastic sinter filter (exchangeable), to exactly detect the relative humidity (0…100% RH) and the temperature (–35...+80 °C) and to detect various parameters in humidity measurement. International system of units SI (default) can be switched to Imperial (via Modbus). The pendulum sensor is applied in a non-aggressive, dust-free environment and is suitable for installation in ceilings, ducts and devices. It is used in the refrigeration, air conditioning and clean room technology, engineering rooms, hotels and conference facilities. A long-term stable, digital humidity and temperature sensor guarantee exact measurement results. These measurands are used to internally calculate the following parameters that can be retrieved via Modbus: relative humidity, absolute humidity, mixture ratio, dew point, enthalpy (ignoring atmospheric air pressure) and ambient temperature. Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in curentfree state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Collect
产品编号 1201-6246
Voltage supply 24 V AC (± 20 %) and 15…36 V DC Power consumption < 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC Data points Temperature [°C], relative humidity [% r. h.], dew point [°C], absolute humidity [g/ m3], mixture ratio [g/ kg], enthalpy [kJ/ kg] Temperature deviation typically ± 0.2 K at +25 °C Sensor digital humidity sensor with integrated temperature sensor, low hysteresis, high long-term stability Sensor protection plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable (optional metal sinter filter, Ø 16 mm, L = 32 mm) Measuring range 0...100 % RH (humidity) – 35...+80 °C (temperature) Zero point offset ± 10 % r.H. (humidity) ± 5 °C (temperature) Ambient temperature –30...+70 °C Medium clean air and non-aggressive, non-combustible gases Bus protocol Modbus (RTU mode), address range 0...247 selectable Signal filtering 4 s / 32 s Protective tube stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm Electrical connection 0.2 - 1.5 mm², via push-in terminal Cable connection cable gland, plastic (2x M 20 x 1.5; with strain relief, exchangeable, inner diameter 8 - 13 mm) or M12 connector according to DIN EN 61076-2-101 (optional on request) Cable gland 2x M 20 x 1.5; with strain relief, exchangeable, inner diameter 8 - 13 mm sensor cable PVC, LiYY, 6 x 0.14 mm², KL = approx. 2 m (other lengths optional) Permissible air humidity < 95 % RH, non-precipitating air Protection class III (according to EN 60 730) Protection type IP 65 (according to EN 60 529)* Standards CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014/ 30/ EU |