AERASGARD® KCO2-W LCDPatented quality product (patent no. DE 10 2014 010 719.1)
![]()
收藏
产品编号 1501-3140-7321-200
Voltage supply 24 V AC/ DC (± 10 %) Power consumption < 1.5 W/ 24 V DC typical; < 2.9 VA/ 24 V AC typical; peak current 200 mA Measuring range, CO2 multi-range switching (selectable via DIP switches) 0...2000 ppm; 0...5000 ppm Measuring accuracy, CO2 typically ± 30 ppm ± 3 % of measured value Temperature dependence, CO2 ± 5 ppm/ °C or ± 0.5 % of measured value/ °C (whichever is higher) Pressure dependence ± 0,13 %/ mm Hg Gas exchange by diffusion Warm up time approx. 1 hour Response time approx. 1 minute, minimum flow rate 0.3 m / s (air) Ambient temperature –10...+60 °C Process connection by mounting flange, plastic (included in the scope of delivery) Protective tube PLEUROFORM, material polyamide (PA6), with torsion protection, Ø 20 mm, NL = 202.5 mm, vmax = 30 m/s (air) Electrical connection 0.14 - 1.5 mm2 via terminal screws Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or M12 connector according to DIN EN 61076-2-101 (optional on request) Cable gland M 16 x 1.5, including strain relief, exchangeable, max. inner diameter 10.4 mm Long-term stability < 2 % in 15 years Protection class III (according to EN 60 730) Standards CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014/ 30/ EU |