Product Detail

AERASGARD® KFTM-CO2-W LCD

Patented quality product (patent no. DE 10 2014 010 719.1)

The maintenance-free, microprocessor-controlled AERASGARD® KFTM - CO2 - W and KLQ - CO2 - W duct air quality transmitters with automatic and manual calibration are used for detecting the overall room climate. They measure CO2 within a range of 0...2000 ppm or 0...5000 ppm, air quality (VOC) in one of three selectable sensitivity levels (LOW/MEDIUM (default)/HIGH, temperature within a range of –35...+80 °C as well as relative humidity from 0...100% r.H. The measured values are converted into standard signals of 0-10 V or 4...20 mA (selectable by means of DIP switches). As an option, the measured values can be shown continuously in the illuminated display.

Relative humidity (% r.H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. A digital, long-term stable sensor used as measuring element for relative air humidity and temperature guarantees precise measuring results. The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the sensor is calibrated for standard applications such as the monitoring of residential and conference rooms. Room ventilation on an as-needed basis, improved well-being and increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of employing our AERASGARD® CO2 sensor devices.

No price
Collect
产品编号 1501-8116-7371-200
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 4.8 W/ 24 V DC typical; < 6.8 VA/ 24 V AC typical; peak current 200 mA
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % r. H. (without dew formation)
Deviation of humidity
typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Output, humidity
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range, temperature
–35...+80 °C
Operating range, temperature
–10...+60 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
Sensor, CO2
optical NDIR sensor (non-dispersive infra-red technology)
including atmospheric pressure compensation (up to 1100 mbar)
with automatic and manual calibration
Output, CO2
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Relay output
with potential-free changeover contact 24 V (assignment selectable via DIP switches)
Response time
< 2 minutes
Output
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches, selected variant applies for all outputs),
with offset potentiometer (± 10 % of the measuring range)
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Ambient temperature
–10...+60 °C
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection, Ø 20 mm, vmax = 30 m/s (air)
without filter: NL = 202.5 mm / with plastic filter: NL = 235 mm (optional with metal filter: NL = 227 mm)
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5; including strain relief,
exchangeable
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) housing only! (PLEUROFORM IP 30)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying actual humidity, actual temperature, air quality and / or the actual CO2 content


  • Telephone

    • 19836508612
    • 19836508612