Product Detail

AERASGARD® RFTM-PS-CO2-W (LCD)

Maintenance-free AERASGARD® RPS - SD room air quality measuring transducer with active output, in an elegant plastic housing with snap-on cover, base with 4-hole attachment, for detecting the particulate matter (PM) content (0...500 g/m3).
The transmitter converts the measurand into a standard signal of 0-10 V (fixed).
Maintenance-free, multifunctional AERASGARD® RFTM - PS - CO2 - W room air quality measuring transducer with active/switching output, automatic calibration, in an elegant plastic housing with snap-on cover, base with 4-hole attachment, optionally with/without display, for detecting air humidity (0...100% r.H.), temperature (0...+50°C), particulate matter (PM)
(0...50/100/300/500 g/m3) and CO2 content (0...2000 / 5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).

No price
Display
  1. Yes
  2. No
Collect
产品编号 1501-2113-7321-000/1501-2113-7
  • TECHNICAL DETAILS
  • DOWNLOADS
Long-term stability (PM)
± 1.25 g/m3 (± 1.25 % of measured value/year)
Measuring accuracy (PM)
typically ± 10 g/m3 (± 10 % of measured value) at PM 2.5
typically ± 25 g/m3 (± 25 % of measured value) at PM 10
Measuring range (PM)
0... 50 g/m3 0...100 g/m3 0...300 g/m3 0...500 g/m3
Particle size (PM)
PM 2,5 (0,3...2,5 m); PM 10 (0,3...10 m)
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
RPS-SD: < 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
RFTM-PS-CO2-W: < 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA

Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % r. H. (without dew formation)
Deviation of humidity
typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Output, humidity
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range, temperature
0...+ 50 °C (output equivalent to 0 -10 V or 4...20 mA)
Operating range, temperature
0...+50 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
0 -10 V or 4...20 mA (selectable via DIP switches)
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Measuring range, CO2
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Sensor, CO2
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Output, CO2
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Relay output
with potential-free changeover contact (24 V / 1 A)
(assignment selectable via DIP switches, switchpoint adjustable)
Warm up time
approx. 1 hour
Response time
< 2 minutes
Output
0 -10 V or 4...20 mA (selectable via DIP switches,
selected variant applies for all outputs), working resistance < 800 Ω
Output
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches, selected variant applies for all outputs),
with offset potentiometer (± 10 % of the measuring range)
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
98 x 98 x 33 mm (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU