Home >> PRODUCTS >>BUS SENSORS >>Modbus >>Temperature Sensors - Modbus >> Rymaskon 612-MOD-RH-CO2-AI
Product Detail

Rymaskon 612-MOD-RH-CO2-AI

The RYMASKON® 500 / 600 / 700 series of room control units has been designed for controlling climate zones in residential, hotel and office rooms and regulating the required indoor heating/cooling steps individually. A colour touch display with modern icons is used for visual control and operation on site. The product range is characterised by a wide variety of combination options for the individual devices.

The RYMASKON® 600 Controller series regulates up to two heating or cooling valves (6-way valves can also be controlled) and the ventilation (EC fan)regulates through analogue outputs (0–10 V). Solar protection, such as shutters or Venetian blinds, can be controlled in two zones via fieldbus. Two external temperature sensors (NTC10K) or two analogue sensors (0–10 V) can be connected in addition to the integrated temperature sensor. Measuring elements for relative humidity and CO2 are also available. The devices are used in room climate engineering, including convector fans, cooling ceilings and heating/cooling systems. Wall mounting is performed on standard flush in-wall boxes. The control units are available with a Modbus or BACnet communication interface and in various type versions (see number key).
The basic RYMASKON® 610 Controller with a 3.5" colour touch display in a white housing has an integrated temperature and humidity sensor (CO2 sensor optional), 2 analogue inputs for external sensors (0–10 V), 1 digital input, 3 analogue outputs (0–10 V), and is available with Modbus or BACnet connection. These room devices are used for controlling temperature, fans and solar protection (2 zones) directly via the analogue outputs or via the bus.


No price
Collect
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/DC (± 15 %)
Power consumption
max. 1.92 W
Measuring range, humidity
0...100 % r. H.
Deviation of humidity
typically ±2 % r.H. (20...80 % r.H.) at +25 °C
Measuring range, temperature
–40...+125 °C
Temperature deviation
typically ±0.5 °C at +25 °C
Temperature sensor
integrated temperature sensor
Inputs
2 analogue inputs 0–10 V
1 digital input (potential-free), Impedance <1 kOhm
Output
3 analogue outputs 0–10 V (heating, cooling, fans)
input impedance > 100 kOhm
Operating mode
Comfort, ECO, OFF, Boost, Frost Protection
Measuring range, CO2
0...5000 ppm
Sensor, CO2
optical NDIR sensor,
(non-dispersive infra-red technology)
with automatic calibration
Ambient temperature
0...+50 °C (operation); –30...+70 °C (storage)
Measuring accuracy, CO2
typically ±50 ppm ±3 % of the measured value at +25 °C
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Installation
wall mounting or on in-wall flush box, Ø 55 mm
Permissible air humidity
0...95 % r. H., (non-precipitating air)
Protection type
IP 20 (according to EN 60 529)
Operating elements
3.5" touch display with backlighting,
cut-out approx. 50 x 75 mm, resolution 320 x 480 pixels, 255,000 colours
Function
temperature and fans (1 zone),
sun protection hood (2 zones)
Communication
Modbus RTU Slave
address range can be configured between 1...247
RS 485 interface, max. 63 devices,
9600 / 19200 / 38400 / 57500 / 76800 Baud,
none / even / odd parity, 1 / 2 stop bits
Housing
plastic, polycarbonate material, self-extinguishing, white colour (optionally black or chrome), weight approx. 220g
Housing dimensions
approx. 88 x 112 x 20.5 mm (on-wall)
approx. 52 x 53 x 28.5 mm (in-wall)
Dimensions
approx. 88 x 112 x 14.5 mm (on-wall)
approx. 88 x 112 x 20.5 mm (on-wall with CO2 sensor)
approx. 52 x 53 x 28.5 mm (in-wall)
Standards
CE conformity,
according to EMC directive 2004/108/EU, Low-Voltage directive 2006/95/EU,
according to EN 61000-6-1/3, EN 60730-1, EN 6100-4-2/4/5/11


  • Telephone

    • 19836508612
    • 19836508612
Technical Support: 97建站 | Admin Login
×