首页 >> 产品中心 >>BUS SENSORS >>Modbus >>Air Quality Sensors - Modbus >> RHEASREG® KLGF-Modbus(LCD)
Product Detail

RHEASREG® KLGF-Modbus(LCD)

Electronic RHEASGARD® KLGF duct air flow transmitter with active output, in an impact resistant plastic housing, optionally with/without display, for determining flow velocity in m/s. The measuring transducer converts the measured value into a standard signal of 0-10 V.

ElectronicRHEASREG® KLSW duct air flow monitor with switching output (one-step or two-step relay), in a plastic housing, for determining flow velocity in m/s. Fine adjustment of the measuring range end value by the user is possible with the help of a potentiometer.
The flow sensor devices are suitable for monitoring or controlling airflow in ducts, at ventilators and dampers, for flow-dependent monitoring of humidifiers and electric heating registers according to DIN 57100, part 420, or for use in connection with DDC systems.



No price
Display
  1. Yes
  2. No
Collect
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/ DC (± 10 %)
Start bridging
0...120 s (can be set via Modbus)
Measuring range, temperature
0...+50 °C
Measuring accuracy
0.5 m/s + 3 % measured value
Warm up time
< 2 min
Response time
< 60 s
Sensor
Calorimetric, temperature compensated, sensor breakage protection, with manual zero-point calibration (via button)
Reproducibility
± 1.0 % final value
Current consumption
approx. 4 VA
Measuring range
0,1...20 m/s
Ambient temperature
storage –20...+ 50 °C
operation 0...+ 50 °C
Medium
pollutant-free, non-precipitating air
Process connection
by mounting flange
(included in the scope of delivery)
Max. sensor cable length
50 m, avoid laying parallel with mains voltage-carrying lines,
or use shielded cables, minimum cross section 1.5 mm2
per conductor, apply cable screen one-sided
Protective tube
PLEUROFORMTM, material polyamide (PA6), with torsion protection, Ø 20mm, NL = 221 mm, vmax = 30 m/s (air), stainless steel V2A (1.4301), Ø 16 mm available upon request as an option
Electrical connection
0.2 - 1.5 mm2, via push-in terminal
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Long-term stability
± 0.5 % final value per year
Humidity
< 98% r.H. pollutant-free, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Optional
Display with illumination, three-line, cutout approx. 70 x 40 mm (W x H), to display the flow velocity, volume flow and temperature (cyclical) or a selectable parameter (static)