Product Detail

AERASGARD® ACO2-SD-U

Maintenance-free AERASGARD® ACO2-SD on-wall air quality measuring transducer with active output, automatic calibration (fixed), in an impact resistant plastic housing with quick-locking screws, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V.

Maintenance-free AERASGARD® ACO2-W on-wall air quality measuring transducer with active/switching output, automatic calibration (can be deactivated), in an impact resistant plastic housing with quick-locking screws, optionally with/without display, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).

The sensor devices are used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

No price
Collect
产品编号 1501-7110-1001-200
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Ambient temperature
–10...+60 °C
Process connection
by screws
Protective tube
stainless steel V2A (1.4301), Ø 16 mm, NL = 55 mm
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5; including strain relief,
exchangeable
Long-term stability
< 2 % in 15 years
Relay output
without changeover contact
Protection class
III (according to EN 60 730)
Warm up time
approx. 1 hour
Protection type
IP 65 (according to EN 60 529)*
Response time
approx. 1 minute
Output
0 -10 V (fixed)
Output
0 -10 V or 4...20 mA (selectable via DIP switches,
selected variant applies for all outputs), working resistance < 800 Ω
Sensor
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU


  • Telephone

    • 19836508612
    • 19836508612
Technical Support: 97建站 | Admin Login
×
seo seo