THERMASGARD® RPTF 2PENDULUM ROOM TEMPERATURE SENSOR (GLOBE THERMOMETER) THERMASGARD® RPTF 2 The THERMASGARD® RPTF 2 resistance thermometre with passive output is specifically used for temperature detection in larger rooms or halls, for example as a dark radiation sensor. In combination with the positioning of the pendulum sensor in the room and the unform flow of ambient air around the sensor, the measuring method employed by the device delivers excellent measuring results representative of the room. The globe temperature is determined in order to take heat radiation into consideration and to estimate the degree of thermal comfort (operative room temperature). The operative room temperature describes the co-action of heat radiation and heat convection (the globe/air temperature ratio is approx. 70% to 30%).
Collect
Measuring range –5...+60 °C Globe plastic, colour black, Ø = 50 mm Insulating resistance 100 MΩ, at +20 °C (500V DC) Connection cable PVC; 1.5 m, H03VV-F, 2 x 0.25 mm², ends stripped with wire end sleeves (other lengths optional: 3 m, 6 m) sensor cable PVC, H03VV-F, 2 x 0.5 mm², ends stripped with wire end sleeves KL = approx. 1.5 m (other lengths optional) Humidity < 95 % r. H. Protection class III (according to EN 60 730) Protection type IP 65 (according to EN 60 529)* |