PREMASGARD 8148-Modbus LCDMaintenance-free microprocessor-controlled PREMASGARD® 814x - Modbus (Series) with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, connection nozzles for pressure hose (Ø 6 mm), plastic sinter filter (exchangeable), optionally with/ without display, to exactly detect the relative humidity (0…100% RH) and the temperature (–35...+80 °C) in ducts and to measure the differential pressure (max. ± 7000 Pa) in air. International system of units SI (default) can be switched to Imperial (via Modbus). Incl. mounting flange and connection set ASD-06 (2 m connecting hose, two pressure port nipples, screws).
Collect
Voltage supply 24 V AC (± 20 %) and 15…36 V DC Power consumption < 4.8 W/ 24 V DC typical; < 6.8 VA/ 24 V AC typical; peak current 200 mA Data points Temperature, relative humidity, differential pressure Measuring range, humidity Operating range, humidity 0...95 % r. H. (without dew formation) Deviation of humidity Measuring range, temperature –35...+80 °C Temperature deviation typically ± 0.2 K at +25 °C Media temperature –20...+50 °C Type of pressure differential pressure Zero point offset < ± 0.7 % of final value Above- below-pressure máx. ± 50 kPa Sensor protection plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable (optional metal sinter filter, Ø 16 mm, L = 32 mm) Ambient temperature –30...+70 °C Medium clean air and non-aggressive, non-combustible gases Bus protocol Modbus (RTU mode), address range 0...247 selectable Pressure connection with metal connection nozzles for pressure hose Ø 6 mm (optional on request with quick connect for PVC fabric pressure hose Ø 6 mm) Signal filtering 4 s / 32 s Process connection by mounting flange, plastic (included in the scope of delivery) Electrical connection 0.2 - 1.5 mm2, via push-in terminal Measuring range pressure ±500 Pa Housing dimensions 126 x 90 x 50 mm (Tyr 2) Cable gland 2x M 16 x 1.5; including strain relief, exchangeable Long-term stability ± 1 %/ year Sum of Linearity+hysteresis < ± 1 % of final value Media contacting parts ms, Ni, Nylon, PU, Si, PVC with plasticisers Protective tube PLEUROFORM, material polyamide (PA6), with torsion protection, Ø 20 mm, vmax = 30 m/s (air) without filter: NL = 202.5 mm / with plastic filter: NL = 235 mm (optional with metal filter: NL = 227 mm) Temperature drift values ± 0.1 %/ °C Temperature drift values ± 0.1 %/ °C Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or M12 connector according to DIN EN 61076-2-101 (optional on request) Protection class III (according to EN 60 730) Housing plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted/ Phillips head - combination), colour traffic white (similar to RAL 9016), housing cover for display is transparent ! Protection type IP 65 (according to EN 60 529) housing only! (PLEUROFORM IP 30) Standards CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014/ 30/ EU Display three-line display with illumination, programmable, cut-out approx. 70 x 40 mm (W x H), for display actual humidity, actual temperature and / or ACTUAL pressure |