AERASGARD® AFTM-CO2-W (LCD)

Maintenance-free on-wall sensor AERASGARD® AFTM - CO2 - W with active/switching output, automatic calibration (can be deactivated), in an impact resistant plastic housing with quick-locking screws, optionally with/without Display, for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm), the quality in three VOC sensitivity levels (low/ medium/high), the temperature (–35...+80 °C) as well as the relative air humidity (0…100% r.H.). The measuring transducer converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).

The sensor device is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

A long-term stable, digital humidity and temperature sensor guarantees precise measuring results.

The CO2 content is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as the monitoring of residential and conference rooms.

No price
Display
  1. Yes
  2. No
Collect
产品编号 1501-7116-7371-200/1501-7116-7
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 4.8 W/ 24 V DC typical; < 6.8 VA/ 24 V AC typical; peak current 200 mA
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % r. H. (without dew formation)
Deviation of humidity
typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Output, humidity
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range, temperature
–35...+80 °C (output equivalent to 0 -10 V or 4...20 mA)
Operating range, temperature
–10...+60 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
Sensor, CO2
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Output, CO2
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Relay output
with potential-free changeover contact (24 V / 1 A)
(assignment selectable via DIP switches, switchpoint adjustable)
Response time
< 2 minutes
Output
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches, selected variant applies for all outputs),
with offset potentiometer (± 10 % of the measuring range)
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Ambient temperature
–10...+60 °C
Process connection
by screws
Protective tube
stainless steel V2A (1.4301), Ø 16 mm, NL = 55 mm
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5; including strain relief,
exchangeable
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying actual humidity, actual temperature, air quality and / or the actual CO2 content