Product Detail

AERASGARD® RPCO2

The RPCO2 air quality sensor detects the CO2 concentration of the ambient air in the range of 0-10000 ppm via a non-dispersive infrared sensor (NDIR) and converts this measured value into a linear output signal 0-10 V or 4-20 mA. The transmitter is simply suspended as a pendulum in the room, which ensures an accurate measurement result in high rooms.
As an option, the air quality sensor has a potential-free changeover contact and a backlit display. There are 3 different scalings (0-2000 ppm, 0-5000 ppm, 0-10000 ppm) which can be selected via DIP switches.
Zero adjustment in relation to the actual ambient conditions can be performed by manual calibration on the instrument. The air quality sensor performs an automatic self-calibration at regular intervals, ensuring a long-term stable CO2 measurement.


No price
Collect
  • TECHNICAL DETAILS
  • DOWNLOADS
Voltage supply
24 V AC/DC (± 5 %)
Power consumption
Ø 50mA (depending on backlight, peak CO2 measurement 200mA, approx. 50ms)
Operating range, humidity
0...98% r.H., pollutant-free, non-precipitating air
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm; 0...10000 ppm
Sensor, CO2
optical NDIR sensor (non-dispersive infra-red technology)
with automatic and manual calibration
Measuring accuracy, CO2
0...2000 ppm: ±50 ppm + 2% MW, 0...5000 ppm: ±50 ppm + 3% MW, otherwise: ±100 ppm + 5% MW (@ 50%r.H. / 20°C / 1013mbar, Autocal. = on)
Pressure dependence
0.16% of measured value/hPa Difference to 1013mbar
Warm up time
10 min
Response time
< 5min
Output
0 - 10V/ 4-20mA, 3-wire connection
Measuring range
0..10 000ppm (optional 20 000ppm or 50 000ppm)
Operating temperature
0...+50 °C
Storage temperature
-20...+50°C
Connection cable
PVC, 2m
Protective tube
Ø25x 80mm
Electrical connection
0.14 - 1.5 mm2 via terminal screws
Housing
Polycarbonate with hinge locks
Color signal white (similar to RAL 9003)
Cable gland
M 16 x 1.5; including strain relief
Dimensions
90,9 x 80 x 48mm
Long-term stability
±1% EW/ Year
Protection class
III (according to EN 60 730)


  • Telephone

    • 19836508612
    • 19836508612
Technical Support: 97建站 | Admin Login
×